New Jersey utility adopts UV AOP treatment to remove 1,4-dioxane from drinking water

0

A New Jersey water utility has installed ultraviolet advanced oxidation (UV AOP) systems at three drinking water treatment plants to address groundwater contamination from 1,4-dioxane, a persistent chemical that is difficult to remove using conventional treatment methods.

New Jersey’s Merchantville–Pennsauken Water Commission (MPWC), which supplies drinking water to approximately 47,000 residents, worked with Trojan Technologies, based in London, Ontario, to implement the systems at its Woodbine, National Highway and Frosthoffer treatment facilities.

1,4-Dioxane is a synthetic chemical used primarily as an industrial solvent and stabilizer. It can also occur as a trace manufacturing byproduct in consumer products such as shampoos, detergents and cosmetics. The U.S. Environmental Protection Agency classifies the chemical as a likely human carcinogen.

The contaminant is highly soluble in water and resistant to natural degradation, allowing it to persist in groundwater for extended periods. Monitoring conducted by the EPA between 2013 and 2015 identified some of the highest concentrations of 1,4-dioxane in the northeastern U.S.

Subscribe to our Newsletter!

The latest environmental engineering news direct to your inbox. You can unsubscribe at any time.

New Jersey is considering a recommended maximum contaminant level of 0.33 micrograms per litre for 1,4-dioxane. Previous monitoring found that approximately 8% of the state’s water treatment facilities had concentrations exceeding that proposed limit.

According to a Trojan Technologies case study, investigations identified both 1,4-dioxane and per- and polyfluoroalkyl substances (PFAS) in the aquifer supplying MPWC, prompting the utility to evaluate treatment options for both contaminants.

The selected UV AOP technology uses ultraviolet light and hydrogen peroxide to generate highly reactive hydroxyl radicals that break down 1,4-dioxane through oxidation. The three installations are designed to achieve contaminant reductions ranging from more than 50% to more than 82%, depending on the facility.

Trojan selected low-pressure UV lamps after preliminary water quality testing identified elevated nitrate concentrations of approximately 16 mg/L (as N). High nitrate levels can interfere with UV treatment by absorbing ultraviolet light and reducing the availability of radicals needed to degrade contaminants.

Low-pressure lamps operate at wavelengths less affected by nitrate absorption, helping maintain treatment efficiency while limiting energy consumption.

Because UV AOP is not effective at removing PFAS, the utility paired the technology with downstream granular activated carbon filtration. The carbon filtration system removes PFAS compounds while also eliminating residual hydrogen peroxide from the oxidation process.

The treatment systems can automatically adjust UV intensity and hydrogen peroxide dosing in response to changing flow rates, while operators can modify contaminant removal targets to accommodate changing groundwater conditions.

According to Trojan case study, the combined treatment approach allows the utility to address both classes of contaminants while managing energy consumption and operating costs.